SF-042 - Gas Valve Diagnostics 2 STG
print icon

See Bulletin

 

This is regarding goodman 2 stage gas valve issues. Typically these are misdiagnosed.

 

In order to have High fire both M and H on the valve must be energized. If only the H is energized, it will still clunk, but no gas flow. 

 

 

See bulletin for more information.