Navien Heat Pump & Hydro Furnace Technical Installation Guide- With notes not in the service manual.
Technical Review for Professional Installers
Document Purpose: This technical guide provides critical installation specifications, operational parameters, and troubleshooting information for Navien Heat Pump (ODU) and Hydro Furnace (NPF Series) systems. All information should be cross-referenced with current manufacturer installation manuals.
1. HEAT PUMP OUTDOOR UNIT (ODU) SPECIFICATIONS
1.1 Operating Envelope
Capacity Performance:
- Full heating capacity maintained down to -4°F ambient
- Changeover temperature adjustable with lowest setting at -4°F
- Designed for cold climate operation
Critical Operating Note: The unit maintains rated capacity significantly lower than conventional air-source heat pumps, making it suitable for northern climate installations.
1.2 Physical Installation Requirements
Clearance Specifications:
- 24 inches minimum service clearance on accessible side
- 60 inches minimum clearance above unit (required for airflow and service)
- Minimum 18 inches elevation above grade (prevents snow/ice obstruction)
Installation Best Practices:
- Elevate unit above historical maximum snow depth for your region
- Ensure level installation both side-to-side and front-to-back
- Locate away from roof valleys and eaves (prevents ice/water damage)
- Provide adequate drainage for condensate and defrost water
- Position to minimize noise transmission to occupied spaces
1.3 Refrigerant Line Set Installation
Line Set Specifications:
- Maximum line set length: 50 feet
- Factory precharged for 25-foot line sets
- Additional refrigerant required: 0.54 oz per foot beyond 25 feet
Oil Trap Requirements (Critical for Proper Operation):
- 16' to 33' vertical rise: Install ONE oil trap
- 33' to 50' vertical rise: Install TWO oil traps
- Oil traps ensure proper oil return to compressor
Line Set Replacement:
- Line set replacement is optimal for reliability
- Use only approved refrigerant line sets
- Maintain proper insulation throughout entire length
Pressure Testing Protocol:
- Use coil maximum pressure rating for nitrogen pressure test
- CRITICAL STARTUP PROCEDURE: Open suction service valve FIRST
- Failure to follow this sequence can cause compressor damage
- Always verify valve position before energizing unit
Refrigerant Connections:
- Use proper flare techniques or approved press fittings
- Apply refrigerant-compatible oil to connection surfaces
- Torque all connections to manufacturer specifications
- Perform leak test at full operating pressure
1.4 Electrical Requirements & Protection
Control Wiring:
- Thermostat wire: 18 AWG suitable up to 100 feet
- Use shielded or twisted pair for runs exceeding 50 feet in commercial applications
Voltage Protection (REQUIRED):
- Install line voltage surge protection on power supply
- Install additional surge protection on control circuit
- Unit includes built-in manual reset thermal protection
Power Supply:
- Verify voltage is within ±10% of nameplate rating
- Dedicated circuit required per NEC/CEC requirements
- Proper equipment grounding essential
1.5 Control Switch Settings (DIP Switches)
SW2-4: Reversing Valve Control
- ON (Factory Default): "O" terminal energized in cooling
- OFF: "B" terminal energized in heating
- Match to thermostat/controller requirements
SW2-2: Adaptive Defrost Mode
- Leave at factory setting for optimal performance
- Adaptive defrost monitors actual coil conditions
- More efficient than time-temperature defrost
SW2-3: Powerful Defrost Mode
- Enable for lakefront or high-moisture installations
- Reduces heating output approximately 10% during operation
- Adaptive defrost (SW2-2) still preferred for most installations
SW3-1, SW3-2: Unit Tonnage Adjustment
- Must match actual installed outdoor unit capacity
- Refer to installation manual for switch position table
SW3-3, SW3-4: ACC Cooling Mode
- Enables enhanced dehumidification in cooling mode
- Modifies compressor ramping timing for humidity control
- Recommended for humid climates
1.6 Commissioning & Startup Procedures
Pre-Startup Requirements:
- Minimum 2-hour crankcase heater energization before startup in cold ambient conditions
- Verify all electrical connections and proper voltage
- Confirm refrigerant line connections are leak-free
- Check condensate drain is clear and properly pitched
Forced Operating Modes:
- Forced Cooling Mode: Clears refrigerant from accumulator (use during commissioning)
- Forced Defrost: Available for testing defrost cycle operation
Airflow Verification:
- Required airflow: 350-450 CFM per ton of cooling capacity
- Measure and document actual airflow during commissioning
- Adjust blower speed as necessary to achieve proper CFM
2. NAVIEN HYDRO FURNACE (NPF SERIES) SPECIFICATIONS
2.1 Model Lineup & Electrical Requirements
Available Models:
- NPF-60: 60,000 BTU/hr (9,000-60,000 modulating capacity)
- NPF-80: 80,000 BTU/hr (modulating capacity)
- NPF-100: 100,000 BTU/hr (14,000-100,000 modulating capacity)
Configuration Options:
- Upflow models (U suffix)
- Horizontal models (H suffix)
- B-width and C-width cabinets available
Electrical Circuit Requirements:
- NPF-60 & NPF-80: 15-amp dedicated circuit
- NPF-100: 20-amp dedicated circuit
2.2 Performance Characteristics
Efficiency & Modulation:
- 97% AFUE rated efficiency
- True modulation: 15% to 100% capacity
- Variable-speed ECM blower motor
- Can sustain airflow up to 0.8" - 1.0" external static pressure
Temperature Control:
- Built-in return air sensor
- Built-in supply air sensor
- Outdoor sensor input available (enables outdoor reset function)
LP Conversion:
- LP (propane) conversion kit included with unit
- Field-convertible from natural gas
2.3 Heat Exchanger Design
Sealed Combustion Chamber:
- Combustion chamber isolated from conditioned airstream
- Airflow passes over hydronic coil only (not combustion chamber)
- Results in quieter operation and improved humidity control
Operating Temperatures:
- Maximum heat exchanger temperature: 155°F
- Lower operating temperature than conventional furnaces
- Minimizes humidity loss from conditioned air
- 42°F freeze protection: Maintains unit warmth during off-cycle
Heat Transfer:
- Dual stainless steel heat exchangers
- Water heated in sealed combustion section
- Heat transferred to air via separate hydronic coil
- Limited lifetime warranty on heat exchanger
2.4 Water System Specifications
System Capacity & Fill:
- Contains 2.5 gallons of spring water (factory-filled)
- Manual water fill recommended for proper air cushion
- Air cushion at top of system serves as expansion device
- Can operate with up to 3/4 water volume depleted (emergency operation only)
Glycol Requirements:
- System rated for up to 30% glycol concentration
- Recommended: 10-15% glycol for freeze protection in conditioned spaces
- Use only approved propylene glycol for potable water systems
Annual Maintenance (CRITICAL):
- Verify water level annually
- High supply temperatures can gradually push water out of system
- Document water level and glycol concentration during service
- Top off as necessary with proper glycol mixture
2.5 Installation Requirements
Location Restrictions:
- MUST be installed in CONDITIONED SPACE ONLY
- Never install in unconditioned attics, garages, or crawlspaces
- Freezing can occur despite 42°F protection in extreme conditions
Mounting & Connections:
- Remove plastic drain cap before installation (factory-installed for shipping)
- Secure ductwork to supply-side flange only
- Do NOT screw into unit cabinet (prevents vibration transmission)
Outdoor Sensor:
- Installation of outdoor sensor enables supply air temperature reset
- Adjusts supply temperature based on outdoor conditions
- Improves comfort and efficiency
2.6 Venting Requirements
Venting Materials:
- 2" PVC Schedule 40 or CPVC approved for condensing appliances
- Dedicated intake and exhaust required (no common venting)
Concentric Venting:
- Concentric vents are allowed per code
- NOT RECOMMENDED by manufacturer
- Can cause combustion air recirculation issues
- Separate intake/exhaust preferred for reliability
Venting Limitations:
- 40,000 BTU limit for concentric venting on modulating units
- Exceed this only with separate intake/exhaust
2.7 Common Installation Issues & Solutions
Pump Impeller Issue:
- Factory test-firing can leave water residue in pump housing
- May cause grime/sludge accumulation stopping impeller
- SOLUTION: Use long screwdriver to gently tap pump body and free impeller
- Verify pump operation before final startup
Combustion Setup (CRITICAL):
- CO₂ values must be within 0.5% of target
- Use combustion analyzer for proper setup
- Document readings for warranty and service records
- Verify readings at both low-fire and high-fire
2.8 Control Features & Service Tools
EZ-Nav Control Panel:
- Built-in setup wizard (simplifies initial configuration)
- Clear text display for diagnostics
- Built-in service wizard
Service Wizard Features:
- Password: 1234
- Complete diagnostic routine: approximately 10 minutes
- Tests performed:
- Air delivery system
- Water circulation system
- Combustion system
- Overall operation verification
- Measures blower current (before and after cleaning)
- Tests combustion blower operation
- Time/date stamps all error codes
Operating Profiles:
- Profile D: Modulating air conditioning mode
- Profile A: Heating mode operation
Connectivity:
- Bluetooth capability for diagnostics
- CHK button allows viewing of operating parameters in real-time
- Mobile app available for troubleshooting
Service Manual Access:
- Service manual ONLY available through mobile app
- Contractors must register as authorized servicers
- Required for detailed troubleshooting procedures
2.9 Maintenance Access
Routine Maintenance:
- Access to blower assembly similar to conventional furnace
- Complete teardown to coil and blower: approximately 1 hour
- Annual maintenance critical for warranty compliance
3. SYSTEM INTEGRATION & OPTIMIZATION
3.1 Coil Sizing for Optimal Performance
Oversizing Strategy:
- Recommendation: ½ ton oversized coil for enhanced dehumidification
- Example: 3-ton heat pump can use 4-ton coil
- CRITICAL: Must install 3-ton TXV (match to outdoor unit, not coil)
- Oversized coil reduces air velocity for better moisture removal
Benefits of Proper Coil Sizing:
- Improved dehumidification in cooling mode
- Lower leaving air temperatures
- Reduced cycling in mild weather
3.2 Thermostat Requirements
Minimum Requirements:
- 4H/2C thermostat recommended for heat pump systems
- Must support multi-stage heating and cooling
Navien Thermostat:
- Specifically designed for NPF hydro furnace integration
- Enables full advantage of modulating capabilities
- Communicates directly with furnace controls
- Recommended for optimal system performance
3.3 Zoning System Considerations
Control Strategy:
- Operate in variable air volume (VAV) mode
- Do NOT use constant volume mode
- VAV provides better comfort and efficiency in zoned applications
Advanced Control:
- System can maintain return air temperature
- Removes thermostat from control equation for certain zones
- Provides more stable operation in multi-zone applications
3.4 Control & Troubleshooting Resources
Built-in Diagnostics:
- CHK button provides real-time parameter viewing
- Bluetooth connectivity for remote monitoring
- Mobile app integration for advanced diagnostics
Troubleshooting Support:
- Use mobile app for guided troubleshooting
- Service manual exclusively available in app
- Register as authorized servicer for full access
- Contact Navien Technical Support: 1-800-519-8794
Operational Intelligence:
- Furnace automatically adjusts both water flow and airflow
- Maintains programmed leaving air temperature setpoint
- Self-diagnostics alert to potential issues before failure
4. WARRANTY INFORMATION
4.1 Standard Warranty Coverage
Compressor & Parts:
- 10 years when properly registered
- 5 years without registration
- Registration strongly recommended at installation
Labor Coverage:
- 90 days from installation date
- Covers authorized service calls only
Heat Exchanger (NPF):
- Limited lifetime warranty on stainless steel heat exchanger
- Requires annual professional maintenance for validity
4.2 Warranty Requirements
Installation Requirements:
- Must be installed by licensed HVAC professional
- Must follow all manufacturer installation instructions
- Proper commissioning and documentation required
Maintenance Requirements:
- Annual professional maintenance recommended
- Water quality testing for NPF systems
- Combustion analysis documentation
Registration:
- Register all equipment within 90 days of installation
- Provides extended warranty coverage
- Enables warranty claim processing
5. TECHNICAL SUPPORT & RESOURCES
5.1 Navien Technical Support
Contact Information:
- Phone: 1-800-519-8794
- Available for contractor support during installation and service
Online Resources:
- Installation manuals: www.navieninc.com/downloads
- Mobile app: Available for iOS and Android
- Parts information: Navien Parts Portal
5.2 Training & Certification
Navien Service Specialist (NSS) Program:
- Manufacturer-certified training available
- Recommended for contractors installing/servicing Navien equipment
- Provides access to technical resources and support
Continuing Education:
- Regular training updates available
- Product-specific installation courses
- Advanced troubleshooting seminars
5.3 Required Tools & Equipment
Refrigerant System:
- Manifold gauge set (R-410A or current refrigerant)
- Micron gauge for evacuation
- Refrigerant scale (accurate to 0.1 oz)
- Leak detector
- Vacuum pump (5 CFM minimum)
Combustion Analysis:
- Combustion analyzer (required for NPF setup)
- Manometer (gas pressure verification)
- Multimeter
General Tools:
- Torque wrench (refrigerant connections)
- Flaring tool or press fitting tools
- Temperature probes
- Airflow measurement device
6. INSTALLATION CHECKLIST
6.1 Heat Pump (ODU) Installation
- [ ] Verify clearances (24" service, 60" above, 18" elevation)
- [ ] Unit level and properly supported
- [ ] Electrical connections per code, surge protection installed
- [ ] Refrigerant lines properly sized and supported
- [ ] Oil traps installed per elevation requirements
- [ ] Nitrogen pressure test completed successfully
- [ ] System evacuated to below 500 microns
- [ ] Proper refrigerant charge verified by weight
- [ ] Suction valve opened FIRST
- [ ] Control wiring completed and verified
- [ ] DIP switch settings confirmed correct
- [ ] Condensate drain installed and tested
- [ ] 2-hour crankcase heat cycle completed
- [ ] Airflow verified (350-450 CFM/ton)
- [ ] System commissioned and tested in all modes
6.2 Hydro Furnace (NPF) Installation
- [ ] Unit installed in conditioned space
- [ ] Electrical circuit properly sized (15A or 20A)
- [ ] Gas line properly sized and pressure tested
- [ ] Condensate drain installed with proper pitch
- [ ] Venting installed per manual (separate intake/exhaust)
- [ ] Water level verified at proper level
- [ ] Glycol added if required (10-15%)
- [ ] Plastic drain cap removed
- [ ] Supply ductwork attached to flange only
- [ ] Return air properly sealed
- [ ] Outdoor sensor installed (if applicable)
- [ ] Thermostat wired and configured
- [ ] Pump impeller verified operational
- [ ] Combustion analysis performed (CO₂ within 0.5%)
- [ ] Service Wizard diagnostic completed
- [ ] All parameters documented
- [ ] Coil TXV matched to outdoor unit tonnage
- [ ] System registered for warranty
7. CRITICAL SAFETY WARNINGS
⚠️ REFRIGERANT HANDLING
- System uses flammable refrigerant (R-32 in some models)
- No open flames near refrigerant connections
- Proper ventilation required during service
- Follow all EPA regulations for refrigerant handling
⚠️ ELECTRICAL HAZARDS
- Disconnect all power before servicing
- Multiple power sources may be present
- Verify all circuits de-energized before service
⚠️ GAS SAFETY
- Verify gas type matches appliance rating
- Perform leak test on all gas connections
- Ensure proper combustion air supply
- Install CO detectors per local code
⚠️ FREEZE PROTECTION
- NPF must be installed in conditioned space only
- Verify glycol concentration in cold climates
- Never bypass freeze protection controls
8. COMMON INSTALLATION MISTAKES TO AVOID
Heat Pump (ODU):
- Opening liquid valve before suction valve (causes compressor damage)
- Inadequate elevation above snow/ice line
- Missing or incorrectly placed oil traps
- Undersized or oversized line sets
- Skipping nitrogen pressure test
- Improper refrigerant charging
- Neglecting surge protection
Hydro Furnace (NPF):
- Installing in unconditioned space
- Using concentric venting without understanding limitations
- Failing to remove plastic drain cap
- Screwing ductwork directly into unit
- Skipping combustion analysis
- Not verifying water level
- Oversizing coil without matching TXV
- Improper glycol concentration
- Not checking pump impeller operation
DOCUMENT REVISION INFORMATION
Version: 1.0
Last Updated: January 2026
Prepared for: Professional HVAC Installers
Source Material: Navien Installation Manuals, Technical Training Materials, Field Installation Notes
Disclaimer: This document is a technical guide based on field experience and manufacturer documentation. Always refer to the current manufacturer installation manuals and local building codes for final installation requirements. Specifications subject to change without notice.
For the most current installation manuals and technical documentation, visit:
www.navieninc.com/downloads
Navien Technical Support: 1-800-519-8794

