Top 30 HVAC Troubleshooting Questions
15 Air-Conditioning Questions + 15 Gas-Furnace Questions
A practical reference built around the questions technicians commonly bring to technical support. Each question includes
common diagnostic areas to investigate before condemning components.
AIR-CONDITIONING TROUBLESHOOTING
1. Why is my suction pressure too low?
Check: Restricted airflow; low refrigerant charge; refrigeration-circuit restriction; low indoor load.
2. Why is my suction pressure too high?
Check: Excessive airflow or load; compressor problem; metering-device issue; overfeeding evaporator.
3. Why is my head/discharge pressure too high?
Check: Dirty condenser; condenser airflow problem; overcharge; non-condensables; high outdoor temperature.
4. Why is my head pressure too low?
Check: Low charge; low outdoor ambient; low indoor load; compressor not pumping properly.
5. Why is my superheat too high?
Check: Undercharge; restricted TXV/piston; low evaporator airflow; TXV bulb or equalizer problem.
6. Why is my superheat too low?
Check: TXV overfeeding; excess refrigerant; high evaporator load; incorrect TXV bulb installation.
7. Why is my subcooling too high or too low?
Check: Incorrect charge; liquid-line restriction; airflow effects; incorrect use of the manufacturer's target.
8. Why is the evaporator coil freezing?
Check: Dirty filter or evaporator; blower/airflow problem; low refrigerant; metering-device problem; low indoor load.
9. Why isn't the house cooling even though the A/C is running?
Check: Capacity problem; airflow problem; refrigerant problem; duct issue; equipment sizing or building-load issue.
10. Why is my temperature split too high or too low?
Check: Incorrect airflow; refrigerant charge; indoor humidity; sensible vs. latent load; measurement location.
11. Why won't the outdoor unit/compressor start?
Check: Contactor; capacitor; pressure switch; control voltage; compressor overload; failed compressor.
12. Why does the compressor start and then shut off?
Check: Thermal overload; high head pressure; low voltage; weak capacitor; refrigerant issue; compressor mechanical
problem.
13. Why am I getting the correct refrigerant pressures but poor cooling?
Check: Airflow; total system capacity; enthalpy change; duct losses; compressor efficiency; building load.
HVAC Technician Troubleshooting Reference Page 2
14. How do I know whether the problem is refrigerant charge or airflow?
Check: Static pressure; actual CFM; superheat/subcooling; temperature and wet-bulb measurements; delivered BTU
capacity.
15. How do I know if the TXV/metering device is bad?
Check: Restriction vs. undercharge; bulb test; equalizer problem; inlet-screen restriction; proper superheat response.
GAS-FURNACE TROUBLESHOOTING
1. Why won't the furnace do anything when there's a call for heat?
Check: Line voltage; transformer; fuse; thermostat signal; door switch; control board.
2. Why won't the inducer motor start?
Check: No board output; failed inducer; pressure-switch circuit; wiring; control-board issue.
3. Why won't the pressure switch close?
Check: Blocked vent; intake restriction; condensate problem; weak inducer; cracked/leaking tubing; drain/trap issue.
4. Why does the pressure switch close and then reopen?
Check: Marginal draft; wind/venting problem; condensate buildup; inducer performance; improper vent sizing.
5. Why does the igniter glow but the burners don't light?
Check: Gas valve; gas pressure; board output; gas supply; ignition timing.
6. Why do the burners light and shut off a few seconds later?
Check: Dirty flame sensor; poor grounding; flame-signal issue; polarity; control-board problem.
7. Why does the furnace keep tripping the high-limit switch?
Check: Low airflow; dirty filter/coil; blower speed; excessive temperature rise; overfiring; duct restriction.
8. Why is the furnace short cycling?
Check: Limit opening; oversized furnace; thermostat issue; airflow; flame-sensing problem; pressure-switch problem.
9. Why is my temperature rise too high?
Check: Low airflow; incorrect blower speed; restricted ductwork; dirty evaporator; overfiring.
10. Why is my temperature rise too low?
Check: Excessive airflow; underfiring; incorrect gas pressure; incorrect blower setting; measurement error.
11. Why won't the blower motor start?
Check: ECM/PSC motor failure; capacitor; control-board output; incorrect programming; wiring.
12. Why does the furnace run but not heat the house properly?
Check: Input/output capacity; gas pressure; airflow; duct losses; equipment sizing; building heat loss.
13. Why is the furnace making excessive noise or rumbling?
Check: Delayed ignition; burner contamination; gas pressure; inducer; blower wheel; venting/combustion problem.
14. Why is a 90+% furnace producing excessive condensate or having drainage problems?
Check: Incorrect furnace pitch; blocked trap; improper vent slope; drain restriction; collector-box issue; frozen
termination.
15. How do I know whether a combustion problem is caused by the furnace or the venting?
Check: O2/CO2; CO; stack temperature; draft/pressure; gas input; vent/intake configuration; combustion-air
problems.
HVAC Technician Troubleshooting Reference Page 4
THE BIGGER DIAGNOSTIC PATTERN
Airflow: CFM, static pressure, temperature rise/drop, dirty components and duct restrictions.
Refrigeration: Superheat, subcooling, saturation temperatures, refrigerant charge and restrictions.
Electrical: Voltage, amperage, capacitors, motors, controls and wiring.
Sequence of operation: Determine exactly where the equipment stopped in its normal operating sequence.
Combustion / venting: Gas pressure, combustion analysis, draft, pressure switches, condensate and vent
configuration.
Training principle: Teach technicians to identify the diagnostic category and verify system measurements before
replacing parts.