Home > Technicans Corner > Troubleshooting Arzel Pumps and Dampers
Troubleshooting Arzel Pumps and Dampers
print icon

See attachments on how to properly diagnose Arzel dampers and pumps.

 

This is from one of the Arzel Techs:

 

Most conventional HVAC systems shouldn’t exceed an ESP of 0.30 when the ductwork is zoned with the smallest zone calling by itself; design if all zones are open should operate around 0.08-0.10 ESP.

Our dampers will operate in higher pressures, I’ve had them in our lab sealing properly against 0.40 ESP;

Our round dampers with the smaller blade sizes will seal against higher pressures than that since they are frequently used in SDHV application that run up to 0.50 ESP.