Copeland Scroll™ Outdoor Refrigeration Unit X-Line User Manual
TABLE OF CONTENTS
Section Page Section Page
- Introduction.................................................. 4
- Nomenclature................................................ 4
- Electrical/Physical Data................................ 5
- Installation/Piping Instructions..................... 5
- Quick Setup Guide........................................ 6
- User Interface............................................... 7
- Button Descriptions and Key Combinations........ 8
- Changing a Parameter Value.............................. 8
- Entering the Advanced Options Menu................ 8
- Moving Parameters Between the Programming Menu and the Advanced Options Menu 8
- Locking the Keypad............................................. 8
- Unlocking the Keypad.......................................... 8
- Changing Clock Setting........................................ 9
- Refrigerant Selection............................................ 9
- Fast Access Menu................................................ 9
- Alarm Menu........................................................ 10
- How to Program a Hot Key From the Controller (UPLOAD) 10
- How to Program a Controller Using a Hot Key (download) 10
- Manual Stepper Control Mode for Vapor Injection (Low Temp) or Liquid Injection (Medium Temp)10
- Controller Startup............................................... 11
- Bump Start Control Operation............................ 11
- Compressor Stop Program................................ 11
- Crankcase Heater.............................................. 12
- Suction Pressure Control................................... 12
- Fan Control......................................................... 12
6.19.1. Fan Overrides and Error Handling........ 12
-
- Defrost Controls.................................................. 13
- Holiday Defrosts.................................... 13
- Defrost Functionality.............................. 13
- Liquid Line Solenoid Control................. 13
- Enhanced Vapor Injection (EVI) for Low Temperature Units 13
- Defrost Controls.................................................. 13
-
-
- EVI SYSTEM CHECKS
-
(XFAL Units Only).............................................. 14
6.21.3 Constant Liquid Temperature Mode for Low Ambient EVI Injection 14
6.22.1. Medium Temperature DLT Protection Error Handling 14
-
- Over-Current Protection..................................... 14
- Incorrect Phase Sequence Protection (3 Phase Only) 15
- Loss of Phase Protection - Current (3 Phase Only) 15
- Open Run Circuit (Single Phase Only)............. 15
- Open Start Circuit............................................... 15
- Over/Under Voltage Protection.......................... 15
- Phase Imbalance (3 Phase Only)..................... 15
- Compressor Internal Thermal Protection.......... 15
- Fixed High Pressure Control.............................. 16
- Alarm Contact..................................................... 16
- Anti-Floodback Warning..................................... 16
- High Condensing Temperature Warning........... 16
- Condensing Unit Operational Control......... 16
- Physical and Installation Requirements...... 17
- Wiring Diagrams......................................... 20
- Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors 28
- Alarm Codes............................................... 29
- Sensor Values............................................. 31
- Parameters................................................. 32
© 2016 Emerson Climate Technologies, Inc. 1
552-7018-00
Safety Instructions
Copeland Scroll™ compressors are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety. Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on Page 3. These instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow these safety instructions.
Safety Icon Explanation
|
DANGER |
|
|
WARNING |

Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons
|
WARNING |
ELECTRICAL SHOCK HAZARD
•
|
|
|
|
|
WARNING |
PRESSURIZED SYSTEM HAZARD
•
|
|
|
|
|
WARNING |
BURN HAZARD
|
|
|
|
|
CAUTION |
COMPRESSOR HANDLING
|

Safety Statements
- Refrigerant compressors must be employed only for their intended use.
• 
install, commission and maintain this equipment.
• 
- All valid standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment must be observed.
Copeland Scroll™ Outdoor Refrigeration Units provide the many benefits of scroll compressor technology, coupled with advanced diagnostic controls, to ensure reliable performance and operation in foodservice applications.
Electronics are used extensively in its protection and diagnostic features. These features are controlled by an electronic integrated control module. The Dixell™ XCM25D control module with CoreSense™ technology provides control functions related to temperature and pressure control, defrost, and compressor protection.
Units are available in 1.5 to 6 HP for coolers and 2 to 6 HP for freezers. All units are 208/230 volts and are available in single or three phase. All -081 bill of material units come factory equipped with a heated and insulated receiver, service valves, pressure controls, defrost control, filter drier, moisture indicator, crankcase heater, variable speed condenser fan, CoreSense Protection, CoreSense Diagnostics, and two-way communications standard.
Low temperature XFAL units (-40°F to 0°F saturated suction) also feature an accumulator and oil separator. Discharge line temperature control is provided by enhanced vapor injection (EVI).
Medium temperature XFAM units (0°F to +45°F saturated suction) include all the standard features.
Discharge line temperature control is accomplished by suction line liquid injection.
Extended medium temp XFAP units (-25F to +45F saturated suction) feature an accumulator. Discharge line temperature control is accomplished by suction line liquid injection.
The Dixell XCM25D Electronic Control Module with CoreSense technology (control module) on Copeland™ condensing units provides many benefits to the contractor and end-user. It is designed specifically for demanding refrigeration applications to ensure simple installation and precision operation. While the control module replaces existing adjustable low pressure controls, fan cycle switches and other relays, it also has additional features. These features include bump start, data storage, communication, and short cycling protection.
The control module is preprogrammed with the proper settings, resulting in little to no setup time. The unit comes with instructions showing how to adjust the low pressure cut-in and cut out. See the label on the inside of the enclosure for more information.
Condensing unit operating range: -40°F to +120°F
|
X |
F |
A |
M |
– |
0 |
2 |
0 |
Z |
– |
T |
F |
C |
– |
0 |
8 |
1 |
|
Family = X-Line |
F = Multi-refrigerant |
A = Air-Cooled |
L = Low Temp M = Medium Temp P = Multiple Applications |
|
1.5 to 6.0 = H.P. |
Z = Scroll |
|
CFV = 208/230V-1ph- 60Hz TFC = 208/230V-3ph- 60Hz |
|
0 = UL Listed Product |
81 = Standard |
|||||
|
Base Model |
Electrical |
Bill of Material |
||||||||||||||
- Electrical/Physical Data
|
Model |
Compressor |
# of Fans |
Overall Dimensions (in) |
Refrigerant Connections |
Receiver Capacity (Lbs @ 90% Volume) |
MCA |
Max Fuse* |
Defrost Relay Rating† (Amps) |
Ship Weight (lbs) |
|||||||||||||||||||||
|
L |
W |
H |
Liquid |
Suction |
R-134a |
R-22 |
R-404A |
R-407A |
R-407C |
R-507A |
R-448A* |
R-449A* |
||||||||||||||||||
|
XFAL-020Z-CFV |
ZXI06KCE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
N/A |
N/A |
9.1 |
10 |
10 |
9.1 |
NA |
NA |
21.55 |
35 |
40 |
246 |
|
|||||||||||
|
XFAL-020Z-TFC |
ZXI06KCE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
N/A |
N/A |
9.1 |
10 |
10 |
9.1 |
NA |
NA |
16.18 |
25 |
40 |
246 |
|
|||||||||||
|
XFAL-030Z-TFC |
ZXI09KCE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
N/A |
N/A |
9.1 |
10 |
10 |
9.1 |
NA |
NA |
17.18 |
25 |
40 |
246 |
|
|||||||||||
|
XFAL-035Z-CFV |
ZXI11KCE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
N/A |
N/A |
9.1 |
10 |
10 |
9.1 |
NA |
NA |
34.05 |
50 |
40 |
272 |
|
|||||||||||
|
XFAL-040Z-CFV |
ZXI14KCE-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
N/A |
N/A |
13.4 |
14.8 |
14.7 |
13.4 |
NA |
NA |
40.1 |
60 |
40 |
274 |
|
|||||||||||
|
XFAL-040Z-TFC |
ZXI14KCE-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
N/A |
N/A |
13.4 |
14.8 |
14.7 |
13.4 |
NA |
NA |
27.1 |
45 |
40 |
312 |
|
|||||||||||
|
XFAL-050Z-TFC |
ZXI15KCE-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
N/A |
N/A |
13.4 |
14.8 |
14.7 |
13.4 |
NA |
NA |
28.85 |
45 |
40 |
323 |
|
|||||||||||
|
XFAL-051Z-CFV |
ZXI16KCE-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
N/A |
N/A |
13.4 |
14.8 |
14.7 |
13.4 |
NA |
NA |
44.73 |
70 |
40 |
343 |
|
|||||||||||
|
XFAL-060Z-TFC |
ZXI18KCE-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
N/A |
N/A |
13.4 |
14.8 |
14.7 |
13.4 |
NA |
NA |
33.98 |
50 |
40 |
341 |
|
|||||||||||
|
XFAM-015Z-CFV |
ZS09KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
13.55 |
20 |
40 |
218 |
|
|||||||||||
|
XFAM-015Z-TFC |
ZS09KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
11.05 |
15 |
40 |
219 |
|
|||||||||||
|
XFAM-017Z-CFV |
ZS11KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
16.8 |
25 |
40 |
219 |
|
|||||||||||
|
XFAM-017Z-TFC |
ZS11KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
14.05 |
20 |
40 |
219 |
|
|||||||||||
|
XFAM-022Z-CFV |
ZS15KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
20.68 |
35 |
40 |
220 |
|
|||||||||||
|
XFAM-022Z-TFC |
ZS15KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
14.3 |
20 |
40 |
219 |
|
|||||||||||
|
XFAM-030Z-CFV |
ZS21KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
30.05 |
50 |
40 |
236 |
|
|||||||||||
|
XFAM-030Z-TFC |
ZS21KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
20.05 |
30 |
40 |
236 |
|
|||||||||||
|
XFAM-045Z-CFV |
ZS33KAE-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
37.35 |
60 |
40 |
285 |
|
|||||||||||
|
XFAM-045Z-TFC |
ZS33KAE-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
29.98 |
50 |
40 |
280 |
|
|||||||||||
|
XFAM-050Z-CFV |
ZS38K4E-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
41.85 |
70 |
40 |
292 |
|
|||||||||||
|
XFAM-050Z-TFC |
ZS38K4E-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
28.85 |
45 |
40 |
292 |
|
|||||||||||
|
XFAM-060Z-TFC |
ZS45K4E-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
31.98 |
50 |
40 |
299 |
|
|||||||||||
|
XFAP-015Z-CFV |
ZS09KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
13.55 |
20 |
40 |
233 |
|
|||||||||||
|
XFAP-015Z-TFC |
ZS09KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
11.05 |
15 |
40 |
234 |
|
|||||||||||
|
XFAP-017Z-CFV |
ZS11KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
16.8 |
25 |
40 |
234 |
|
|||||||||||
|
XFAP-017Z-TFC |
ZS11KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
14.05 |
20 |
40 |
234 |
|
|||||||||||
|
XFAP-022Z-CFV |
ZS15KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
20.68 |
35 |
40 |
235 |
|
|||||||||||
|
XFAP-022Z-TFC |
ZS15KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
14.3 |
20 |
40 |
234 |
|
|||||||||||
|
XFAP-030Z-CFV |
ZS21KAE-PFV |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
30.05 |
50 |
40 |
251 |
|
|||||||||||
|
XFAP-030Z-TFC |
ZS21KAE-TF5 |
1 |
16.7 |
40.5 33.1 |
1/2 S |
7/8 S |
10.7 |
10.5 |
9.1 |
10 |
10 |
9.1 |
9.7 |
9.7 |
20.05 |
30 |
40 |
251 |
|
|||||||||||
|
XFAP-045Z-CFV |
ZS33KAE-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
37.35 |
60 |
40 |
300 |
|
|||||||||||
|
XFAP-045Z-TFC |
ZS33KAE-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
29.98 |
50 |
40 |
295 |
|
|||||||||||
|
XFAP-050Z-CFV |
ZS38K4E-PFV |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
41.85 |
70 |
40 |
307 |
|
|||||||||||
|
XFAP-050Z-TFC |
ZS38K4E-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
28.85 |
45 |
40 |
307 |
|
|||||||||||
|
XFAP-060Z-TFC |
ZS45K4E-TF5 |
2 |
16.7 |
40.5 48.9 |
1/2 S |
7/8 S |
15.7 |
15.5 |
13.4 |
14.8 |
14.7 |
13.4 |
14.2 |
14.3 |
31.98 |
50 |
40 |
314 |
|
|||||||||||
Generator Requirements: In situations or locations where an electrical power generator is used for backup, the Copeland Scroll Outdoor Refrigeration Unit requires a supply voltage of 186-253 VAC.
A clearance of 8 inches from the wall (or the next unit) is required from the unit’s left and rear panel; a clearance of 20 inches is required from the unit's right, top and front panels. (See diagams in section covering Physical and Installation Requirements) Ensure that the hot discharge air from one unit does not circulate to another unit.
The unit is designed to mount on the ground, on a roof, or on a wall. For ground mounting, the units should be placed on a level solid concrete slab with rubber strips
between the feet and concrete, or other raised support structure. For wall mounting, use a wall bracket system designed for mounting condensing units or universal metal framing strut and follow the manufacturer's instructions. All mounting options must follow local
zoning and building codes.
Pipes should be sized for optimum performance and good oil return, and for the full capacity range through which this particular unit will need to operate. Follow the ASHRAE guidelines for proper piping practice.
EMERSON..
Climate Technologies
Application Engineering
AES-1412 R1
time power is applied or if the
|
clock has lost its setting. |
Press SET to select the
rl:c menu.
|
nrn
Hr f1d ron Er
until "F flashes.
|
0 n,,,• |
|
Press SET and A to exit the rte menu. If SET and A are held, the control will exit
Use the Aor 'v buttons to find the PAr menu, then press SETto select.

|
program mode. Use'v and SET
From main screen,
|
to return to program mode.
0 |
|
|
I p IP

Pct
parameters
ISelect value
I P2P


|
P3t PYt PSt |
Use SET and A 'v
buttons to select and adjust pressure parameters.

E) Set defrost parameters and schedule
IGo to next parameter SET I
|
|
Plt |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||

![]() |
P6t

From the PAr menu, use SET and A 'v buttons to select and adjust defrost parameters.
Press and hold SET and A to exit program mode.
|
,dF rl:JF EdF
Ld I Ld2 Ld3 LdY LdS Ld6
2015ECT·41 (10/15) - 052-7289·02
E-Error L= Lockout
- User Interface
The controller display is shown below along with the function of each light. The controller displays the current suction pressure to three digits in pounds per square inch gage (psig). The controller uses a 7-segment display for digits and the following alpha characters:
The 7-segment alphabet and Roman equivalent:
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A |
b |
C |
d |
E |
F |
H |
i |
L |
M |
n |
o |
P |
q |
r |
S |
T |
U |
Y |
0 |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
The letters G, J, K, Q, V, W, X and Z are not used on the 7-segment display.
![]() |
|
LED |
MODE |
FUNCTION |
|
|
ON |
Compressor enabled |
|
Flashing |
Anti-short cycle delay enabled |
|
|
|
ON |
Condensing fans enabled |
|
|
ON |
Display temperature value in degrees F |
|
Flashing |
Programming mode |
|
|
|
ON |
Display pressure value in PSI |
|
|
ON |
Browsing service menu |
|
Flashing |
Fast access menu (Viewing set points and measured values) |
|
|
|
ON |
Browsing the alarm menu |
|
Flashing |
New alarm occurred |
|
|
|
ON |
An alarm is occurring |
|
|
ON |
In defrost or evap fan drip time when ON |
|
|
ON |
Evaporator fans enabled |
-
- Button Descriptions and Key Combinations
|
|
(SET) Select a parameter or confirm an operation when in programming mode. |
|
|
(RESTART) Hold for 5 seconds to reset any lockouts if the current state of the controller allows for reset. Allows a manual restart and a “dead band reset”. |
|
|
(UP) View current measured values (Fast Access Menu); in programming mode or any menu to browse the parameter codes or increase the displayed value. |
|
|
(DOWN) in programming mode or any menu to browse the parameter codes or decrease the displayed value. |
|
|
(SERVICE) To enter the service and alarm menu. |
|
|
Hold for 3 seconds to start a manual defrost |
|
|
Press and hold for about 3 sec to lock (Pon) or unlock (PoF) the keyboard. |
|
|
Press together to exit from programming mode or from menu; on submenus to return to previous level. |
|
|
Press together for 3 sec to access to first level of programming mode. |
-


Changing a Parameter Value
To change a parameter value:

Hold down keys for 3 seconds or until the 'F' LED starts blinking to enter the module’s programming menu.- Use
or
to select the rtC or PAr menu
Press to enter the menu.- Use
or
to select the required parameter.
Press the key to display its value.- Use
or
to change its value.
Press to store the new value.

TO EXIT: Press or wait 60 seconds without pressing a key.
NOTE: The set value is stored even when the procedure is exited by waiting for the time-out to expire.
NOTE: If a menu does not have any parameters
available, noP will be displayed

Hold down keys for 3 seconds or until the F LED starts blinking to enter the module’s programming menu.- Use
or
to select the PAr menu
Press to enter the PAr menu- Use
or
to select the PAS parameter
Press to select PAS- The blinking PAS label will be showed for a few seconds
- Will be showed 0 - - with blinking 0: insert the password [321] using the keys UP and DOWN and confirming with SET key.
While in the advanced options menu, certain parameters will have a (.period) in between the 2nd and 3rd character, for example Ci.n. These parameters are in the Programming Menu as well as the Advanced Options Menu.
To add or remove a parameter from the programming

menu, press the keys together while the parameter name is on the display in the advanced options menu. The (.period) between the 2nd and 3rd parameter will either be added or removed.

TO EXIT: Press or wait 60 seconds without pressing the keys.
-
- Locking the Keypad
Press the keys for 3 seconds.- The POF message will be displayed and the keyboard will be locked. The Fast Access Menu will remain accessible whil the keyboard is locked.
- If a key is pressed more than 3 seconds the POF message will be displayed.
- Unlocking the Keypad
Press the keys for 3 seconds until the Pon message is displayed.
-




Changing Clock Setting
![]() |

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-
Refrigerant Selection
Using parameter REF set the refrigerant as follows (refer to nameplate for approved refrigerants):
-
- Fast Access Menu
This menu allows viewing measured values from various probes and view some outputs resulting from these measurements. The values nP or noP stand for probe not present or value not evaluated. Err means the value is out of range, probe is damaged, not connected, or incorrectly configured.
Press
to enter the Fast Access Menu.
Use or
arrows to select an entry, then press
to see the value or to go on with other value.

TO EXIT: Press or wait 60 seconds without pressing the keys.
|
|
Refrigerant |
rEF |
|
R-404A |
404 |
|
R-507 |
507 |
|
R-134A |
134 |
|
R-22 |
r22 |
|
R-407C |
07C |
|
R-407A |
07A |
|
R-407F |
07F |
|
R-448A |
48A |
|
R-449A |
49A |
![]() |
-
- Alarm Menu
The controller time-stamps and stores the last 50 alarms. See Section 11 for alarm codes.
|
Action |
Button |
Notes |
|
Enter alarm menu |
|
Push and release alarm key (Displays SEC when alarm menu is active) |
|
Enter alarm list |
|
Press SET to confirm |
|
Scroll through active and recorded alarm list |
Or
|
Scroll the list of alarms and see the list of active alarms with the number of the alarm (Letter+Number, A01-A50). Push Down key and see the alarm Name or Code. Push Down key and see the next active alarm |
|
Select the alarm to see the date and time |
|
Enter the sub menu with alarm time details |
|
Scroll through alarm information data |
Or
|
Successive presses of the down arrow button will display the clock data label (hour, minute, day, month, year) followed by the value of the preceding label. The up arrow will reverse this order and show the value followed by the label. The displayed values record the start time of an alarm. |
|
Exit menu |
|
Press SET and UP together or wait about 10 seconds. |
-
- How to Program a HOT-KEY From the Controller (UPLOAD TO OVERWRITE HOT-KEY)
Caution: Overwrites hot key. When the controller is ON, insert the HOT-KEY into the 5-PIN receptacle (labeled H-K) and push the
button; the UPL message appears followed a by a flashing End label.
Push button and the End will stop flashing. Turn OFF the controller, remove the HOT-KEY and then
turn the controller ON again.
NOTE: the Err message appears in case of a failed programming operation. In this case push the
again if you want to restart the upload again or remove the HOT-KEY to abort the operation.
-
- How to Program a Controller Using a HOT-KEY (Download)
A hot key is included with each unit for factory reset and replacement control programming. Remove power from the unit.
Insert a pre-programmed HOT-KEY into the 5-PIN receptacle (labeled H-K) and reapply power to the unit.
The parameter list of the HOT-KEY will be automatically downloaded into the controller memory. The doL message will blink followed by a flashing End label.
After 10 seconds the controller will restart and begin
working with the new parameters. Remove the HOT-KEY
NOTE: The message Err is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the HOT-KEY to abort the operation.
-
- Manual Stepper Control Mode for Vapor Injection (Low Temp) or Liquid Injection (Medium Temp)
For troubleshooting purposes, the stepper setting can
temporarily be manually adjusted.
From the standard display screen, pressing SET and SERVICE/ALARM key for 3 seconds will enter a manual stepper control mode.
In the manual stepper control mode, the display shows
the current step count of the valve.
In manual stepper control mode, all algorithms controlling the stepper valve are suspended, but the rest of the functions operate normally
The up and down arrows on the keypad open and close the valve, with the display showing the updated step count
If the controller is left untouched for 60 seconds or the set and up button are pressed together to exit, the controller will resume normal operation.
Condensing Unit Operational Control
The X-Line control module operates the condensing unit and ensures the system remains in correct operating conditions. It controls the follow items:
- Compressor
- Condenser Fan Motor(s)
- Crank Case Heater
- Receiver Heater
- Defrost Heater (If connected)
The X-line Unit will protect the system from the following fault conditions (See Sections 6.23 through 6.31 for further details):
- Discharge Line Temperature Protection
- Over-Current Protection
- Incorrect Phase Sequence Protection (3 Phase Only)
- Loss of Phase Protection - Current (3 Phase Only)
- Open Run Circuit (Single Phase Only)
- Open Start Circuit (Single Phase Only)
- Over/ Under Voltage Protection
- Phase Imbalance (3 Phase Only)
- Compressor Internal Thermal Protection
- Fixed High Pressure Control
In addition, the X-Line unit has protection features that will prevent it from reaching a fault condition. For example, when the low temperature unit experiences an extremely hot day, the control module decides to switch from vapor-injection-optimization to discharge gas temperature control to allow the compressor to run safely and pass the extreme weather hours.
-
- Controller Startup
At initial power up, the controller display will display the
following information:
All LEDs will light up for approximately 2 seconds.
For 3 seconds, the controller will display the firmware version (EX: 1.0, 1.1, etc.)
For three seconds the controller will display the
program number (EX: 100, 101, 200, etc.)
The controller will then wait 6 seconds before turning on the compressor or any other device.
Once the controller calls for the compressor to run and there are no active alarms, the controller will then turn on the compressor utilizing bump start (if needed per Section 6.15) and control the fans and compressor.
-
- Bump Start Control Operation
If the ambient temperature sensor reads less than 95°F when the controller is first turned on or after the compressor has been off for 4 hours and now is being turned on, the compressor will initiate a bump start. If the ambient temperature sensor is not functioning, the mid-coil temperature sensor will determine if the unit will initiate a bump start or not.
The compressor and fans will run for 2 seconds then turn off for 15 seconds three times. Once this sequence is completed, the unit resumes normal operation.
The crank case heater will remain off during the bump start sequence.
If liquid injection, vapor injection, or a system EXV is present, the stepper valve will remain closed until the bump start has finished.
In the event of a power loss, the controller can be programmed to enter a defrost at power up if dPo is set to YES. It is turned off by default, but is adjustable from the advanced options menu.
-
- Compressor Stop Program
When the compressor needs to turn off, either based on an error or loss of demand, the following items will occur:
- Liquid or Vapor Injection Only: If a non-error shutdown occurs, compressor runs for 5 seconds before turning off to allow the liquid of vapor injection valves to fully close.
- Compressor turns off
- Condenser fans turn off
Crankcase heater turned on (See Section 6.17)
NOTE: During the pump down process with the 5 second delay the compressor may run down into a vacuum. There are no reliability issues in this application.
-
- Crankcase Heater
The crankcase heater is energized when the ambient temperature is below 50°F and the compressor is off. If an ambient sensor fails, the crankcase heater is energized when the compressor is off.
-
- Suction Pressure Control
The compressor is operated based on the suction pressure cut-in (Cin) and cut-out (CoU). If the suction pressure rises above the cut-in, the compressor is turned on using the startup procedure (See Section 6.14). If the suction pressure then falls below the cut- out, it turns the compressor off using the shutdown procedure (See section 6.16).
The compressor remains off for a minimum 120 seconds (2oF) after shutdown, which is adjustable in the advanced options menu (See section 6.3).
If the suction pressure transducer fails, the compressor will run in limp along mode. The compressor will stay off for 3 minutes (CoF) then run for 3 minutes (Con). These values are adjustable from the advanced options menu (See section 6.3).
The cut-in and cut-out settings are adjustable between 0 PSIG and 135 PSIG.
IMPORTANT: At initial power up, depending on the suction pressure transducer, the suction pressure could be higher than the rating of the transducer. For 15 minutes after power up, any over pressure errors generated by the suction pressure transducer should be ignored, and the display will flash 135. If the transducer is still in an error state after the time has expired, the control will alarm that the suction pressure transducer signal is lost, and go into limp along mode.
-
- Fan Control
The The X-line uses variable speed PSC condenser fan motors to maintain the head pressure values that allow the system to operate within the compressor operating envelope and maintain the minimum pressure differential across the expansion device to allow it to operate properly.
The controller uses a Proportional-Integral (PI) control algorithm to determine the fan speed. The fans will not run any slower than 40% before turning off. When a fan first turns on it will run for 3 seconds at full speed before it begins modulating. Fans will run for at least
10 seconds before turning off and stay off for at least 10 seconds before being turned back on.
Since the X-Line controller knows the current suction pressure, the controller can determine the minimum condensing point for the condition the unit is actually running, and will adjust the fan control set point to maintain that temperature or higher.
The XFAP/XFAM and XFAL models have different compressors and different refrigerant options. Therefore, during commissioning, it is important to identify the seleted refrigerant so the controller will operate the fans properly.
Low ambient operation
The condensing unit can operate in outdoor ambient temperatures as low as -40°F. The unit will automatically adjust condenser fan speed to maintain head pressure. At extremely low ambient temperature the condenser fan might not run, but the condenser coil is still discharging heat. Parameter LAS sets the ambient temperature required to initiate low ambient on time. The default value is -20°F. Parameter LMO sets the low ambient minimum on time. The default value is 6 seconds. Below -20°F ambient, when the condensing unit runs it will run for a minimum of 6 seconds.
IMPORTANT NOTE: To fully utilize low condensing options below 70°F condensing, an electronic expansion valve (EXV) is normally required to handle the larger variation in mass flows. As a result, the unit is shipped with a default minimum condensing override value of 70°F (80°F for XFAL). The fans will still follow the map of the selected refrigerant, but the map will not be allowed to run below the override value. If you have a system with an EXV installed, you can adjust the value by changing parameter MCS in the advanced options menu.
-
-
- Fan Overrides and Error Handling
-
If the discharge line temperature is above 205°F the fans will run at full speed.
If the condenser mid-coil temperature sensor fails, the fan speed is determined by outdoor ambient. If both the outdoor ambient sensor and the condenser mid-coil temperature sensor fail, all fans will run at full speed.
-


Defrost Controls.

![]() |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

-
-
Holiday Defrosts
-
If you are using real time clock mode (rtc), holiday defrosts can be set in the advanced options menu. To set a holiday, change Hd1 from nU to whatever day of the week you would like to have a different defrost schedule. (An example would be if a store is closed on Sundays and needs less defrosts). You can set a second holiday by changing Hd2. The defrosts for the set holidays are controlled by parameters 5d1 through 5d6.
-
-
- Defrost Functionality
-
During a defrost the controller will display dEF.
To manually initiate a defrost, press and hold the defrost
button for 3 seconds.
The controller will terminate defrost after 45 minutes MDF (Pr1 parameter) or after the defrost termination input (Terminal 'X') is closed.
-
-
- Liquid Line Solenoid Control
-
By default, the unit assumes that a liquid line solenoid is used to pump down the system during a defrost. When the unit enters a defrost, the evaporator power (Connection 3 on the terminal strip) will turned off, turning off the liquid line solenoid as well. The unit will then run until the suction pressure drops below the cut out value, then turn off the compressor. When the defrost is complete, the unit will apply power to the evaporator, opening the solenoid and the compressor will start running once the suction pressure is above the cut in.
If a pump down solenoid is not present or the unit should not pump down when entering a defrost, parameter tLS should be set to no. TLS is set to YES by default.
The injection valve is a key part of the EVI system. It regulates vapor injection flow to optimize the performance of system and cool the scroll set. When the compressor first calls for power, the injection valve opens a preset amount before the compressor turns on. After startup, the EVI injection valve is controlled using a proportional-integral (PI) algorithm to control the differential between the vapor inlet temperature and the vapor outlet temperature. The differential is 9°F for R404A, R507, R134a, and R22. It is 18°F for other approved refrigerants. The PI algorithm for the EVI injection valve control is auto-adaptive, so it does not need to be adjusted.
If during normal operation the DLT temperature reaches 225°F the control changes to act as a liquid injection valve to control the DLT temperature. Once the DLT temperature falls below 200°F, normal vapor injection control resumes.
If the discharge temperature goes above 250°F, the compressor trips off and the control displays an E44 error. The compressor cannot turn back on until the temperature drops below 170°F and has been off for 3 minutes.
If the compressor trips more than 4 times per hour (dLn), the controller will lock out the compressor, requiring a manual reset or the controller power to be reset. The controller will display L44 showing the compressor has tripped on high DLT and locked out. If parameter dLn, which is available in the advanced options menu, is set to 0, the unit will always automatically reset.
In case of DLT failure, the injection valve operates based
on the mid coil and ambient sensor.
If the DLT sensor fails and a mid-coil temperature sensor is available, the injection valve will be opened based on the mid coil temperature. If the mid coil sensor fails in addition to the DLT sensor, the injection valve is controlled by the ambient temperature.
-
-
- EVI System Checks (XFAL units only)
-
An E47 warning code means that the injection valve has been fully open longer than 3 minutes. An E48 warning code means that the temperature difference across the EVI heat exchanger is higher than expected for 3 minutes. These are only warnings, but are likely due to loss of refrigerant charge or undercharge
Subcooling is generally good, but liquid refrigerant that is too cold can create sizing problems for TXVs. If the ambient is below 30°F, discharge temperature is generally well under control and so the controller disables vapor injection to operate in constant liquid temperature mode. The low ambient temperature will generate enough subcooling for the system without the need for injection. Emerson recommends a balanced port TXV (or EXV) for low ambient operation.
-
-
- Low Temperature Units With EVI TXV Selection
-
For use with low temperature units with EVI, Emerson recommends a balanced port TXV because it offers a wider operating range for floating liquid temperatures. In addition, the unit liquid line should be insulated since the liquid line temperature will be lower than the ambient temperature.
See the table on page 28 for specifics regarding balanced port sizing recommendations. Applied with the low temp units it is recommended that a balanced port expansion valve be used along with a complete review of the distributor and nozzle (orifice) that is supplied with the evaporator coil being matched with the applicable condensing unit. Typically nozzles are selected for standard TXV sizing using 100°F liquid, with the low temperature X-Line units those typical selections could be grossly oversized. See the table on page 28 for the liquid correction safety factors when selecting those components.
-
- Medium Temperature DLT Protection
Medium Temperature units have liquid injection through the suction line to prevent compressor overheat during extreme ambient operations. The liquid injection will keep discharge temperatures below 235°F.
If the discharge temperature goes above 255°F, the compressor trips and the controller shows an E44 error. The compressor cannot turn back on until the discharge line temperature drops below 170°F and has been off for at least 3 minutes.
If the compressor trips more than 4 times in an hour (dLn) on DLT, the controller will lock out the compressor, requiring a manual reset or the controller power to be reset. The controller will display L44 showing the compressor has tripped on high DLT and is locked out. If parameter dLn, which is available in the advanced options menu, is set to 0, the unit will always automatically reset.
See Section 12 for 86k Thermistor probe resistance values. Discharge line sensor is 86k, all other temperature sensors on this unit are 10k.
-
-
- Medium Temperature DLT Protection Error Handling
-
In case of DLT sensor failure, injection is determined by
the mid coil and ambient sensor.
If the DLT sensor fails and a mid-coil temperature sensor is available, the injection valve will be opened based on the mid coil temperature. If the mid coil sensor fails in addition to the DLT sensor, the injection is determined by the ambient temperature.
Current is measured using the two current transducers installed on the controller. If the current exceeds the compressor MCC, the controller will stop the compressor for 3 minutes and signal error E23. A separate parameter MC2 is available to allow adjust the maximum current value down, but not up, in the advanced options menu.
To avoid any fault triggering during the compressor startup period caused by the high inrush current, current sensing in not processed by the controller until 6 seconds after compressor startup.
If the compressor trips more than 5 times in an hour (default) on high current, the controller will lock out the compressor and display an L23 lockout, requiring a manual reset or the controller power to be reset. If the parameter oCn, which is available in the advanced options menu, is set to 0, then the unit will always reset.
The controller determines whether the sequence of three phase supply lines is proper or not. The voltage sensing terminals are connected to the 3-phase supply of the compressors. If an incorrect phase (L1, L2, and L3) is detected, the controller will trip compressor immediately and display an L21 lockout code. The compressor will not restart until the power to the unit is turned off and L1 and L2 are switched. The reset button will not work with this error.
The unit controller detects whether or not all the three phase supplies are available. If a phase is missing, the controller will shut down the compressor and display an E20 error code and prevent the compressor from restarting for 3 minutes. If the unit is shut down more than 5 times in an hour (default), then unit will lock out and display an L20 lockout code. If the parameter (PEn) is set to 0, the unit will always automatically reset.
After the compressor is started and runs for 6 seconds, if the there is no run circuit current and the start current is still greater than 1 amp, the controller will display an E24 error for open run circuit and shut down the compressor. The compressor will not restart for 3 minutes in the event of a trip.
If the unit is shut down more than 5 times in an hour (oCn), then the unit locks out and display a L24 lockout code. If the parameter (oCn) is set to 0, the unit will always automatically reset.
-
- Open Start Circuit (Single Phase Only)
Immediately after startup, if there is no start current for the first 500ms and the run current is greater than 1 amp, the controller will display an E25 error for open start circuit and shut down the compressor. The compressor will not restart for 3 minutes in the event of a trip. If the unit is shut down more than 5 times in an hour (oCn), then the units locks out and display an L25 lockout code. If the parameter (oCn) is set to 0, the unit will always automatically reset.
-
- Over/ Under Voltage Protection
If the voltage drops below 10% of the minimum rated voltage or above 10% of the maximum rated voltage for 1 second, the controller will shut off the compressor and display an E26 (under voltage) or E27 (over voltage) error code until the voltage is back within acceptable range and the compressor has been off for 3 minutes (oCn).
If the compressor trips more than 5 times per hour (Default), the controller will lock out the compressor, requiring a manual reset or the controller power to be reset. If the parameter (PEn) is set to 0, then the unit will always reset. The controller will display an L26 (lockout, under voltage) or L27 (lockout over voltage).
If the voltage in a given leg drops below 5% of the average voltage of the 3 legs for 1 second, the controller will display E22 and shut the unit down (based on a parameter PiC) for 5 minutes and until the phase imbalance is corrected.
-
- Compressor Internal Thermal Protection
If the compressor’s internal thermal protector trips, the contactor fails, or the contactor is miswired, the controller will detect the loss of current and display an E28 warning code. This happens if both of the current transducers do not sense current for 1 second when the controller sends a compressor run signal. To avoid any fault triggering during the compressor startup period caused by the high inrush current, current sensing is not processed by the controller until 6 seconds after compressor startup.
-
- Fixed High Pressure Control
The high pressure control is a nonadjustable pressure switch that opens at 440 +/- 10 psig and resets at 348psig in the event of high discharge pressure. If the high pressure switch is open, the compressor shuts off immediately, ignoring any overrides. As long as the high pressure switch is open, the compressor will not run. The compressor will stay off for 3 minutes regardless of when the pressure switch resets. E40 will be displayed while the unit is shut down.
If the compressor trips more than 5 times per hour, the controller will lock out the compressor, requiring a manual reset or the unit power to be reset. Error code L40 means the compressor tripped on high pressure and is locked out. If the parameter HPn is set to 0, the unit will always automatically reset.
-
- Alarm Contact
The alarm contact (A1 and A2 on terminal block) is a dry contact that can be wired to an external warning device such as a buzzer or light. This relay has a 5 Amp limit, up to 250V. The alarm contact will close in the event of an alarm or lockout.
-
- Anti-Flood Back Warning
System Liquid Flood Back Warning Logic:
High-side superheat is the discharge line temperature minus the mid-coil temperature. If high-side superheat is less than 18°F for longer than 30 minutes during the last 45 minutes, the controller will display E50, but continue running the system. When the high-side superheat climbs above 18°F for 30 minutes, then the warning signal stops.
-
- High Condensing Temperature Warning
An E46 warning means the condensing temperature exceeded 150°F. The fans will run at full speed but the compressor does not shut down. The warning clears when the temperature drops below 140°F.
- Local and Remote Displays and Communication
The controller can communicate with Modbus RTU RS485 supervisory controllers. An optional remote display is available. The display can be mounted up to 30 feet from the unit. To connect and configure the remote display, follow the instructions included with the remote display
Figure 1
Bottom View
All Models

Figure 2 – Controller
NOTE: There is no field wiring to this controller except for communications. The transformer wired in the unit is for the controller only. Do not tap off the transformer to power any other devices. When removing a connector, do not pull on the wire.
High Voltage Connections
|
Label |
Connector(s) |
Electrical Limit (250VAC Max) |
Function |
|
C1 |
¼” Spade Connectors (2) |
25A Max Current (16A Max Each Spade) |
Provides Power for Defrost Heater and Evaporator Fan Relays |
|
D01 |
¼” Spade Connector |
16A Relay |
Operates 40A Evaporator Fan Relay |
|
D02 |
¼” Spade Connector |
16A Relay |
Operates 40A Defrost Heater Relay |
|
C2 |
¼” Spade Connector |
16A Max Current |
Provides Power to Compressor Relay and CCH/RH Relays |
|
D03 |
¼” Spade Connector |
5A Relay |
Operates Compressor Contactor |
|
D04 |
¼” Spade Connector |
8A Relay |
Powers Crankcase Heater and Receiver Heater |
|
D05 |
¼” Spade Connectors (2) |
5A Relay |
Dry (Switch Only) Alarm Contact |
|
DI1 |
|
250VAC Max |
Left Terminal – Defrost Termination Input Right Terminal – L2 |
High Voltage Connections (continued)
|
Label |
Connector(s) |
Electrical Limit (250VAC Max) |
Function |
|
Neutral |
¼” Spade Connectors (6) |
25A Max Current (16A Max Each Spade) |
L1 Common Terminal Strip |
|
R |
¼” Spade Connector |
480V Max |
L1 Voltage Sensing |
|
S |
¼” Spade Connector |
480V Max |
L2 Voltage Sensing |
|
T |
¼” Spade Connector |
480V Max |
L3 Voltage Sensing (3 Phase Only) |
|
SUPPLY |
|
24VAC, 40VA |
Controller Power Supply |
|
T01 |
|
2A Wave Form Chopping Triac |
Variable Speed PSC Fan Motor Control |
|
T02 |
|
Not Used |
For Future Use |
|
Sensor Connections |
||
|
Label |
Function |
Type |
|
AI1 |
Suction Pressure Transducer |
0.5 to 4.5 VDC Ratio metric |
|
AI2 |
Condenser Temperature Sensor |
10k NTC (See Section 12 for values) |
|
AI3 |
Discharge Line Temperature Sensor |
86k NTC (See Section 12 for values) |
|
AI4 |
EVI Heat Exchanger Inlet Vapor Temperature Sensor (Low Temp Only) |
10k NTC (See Section 12 for values) |
|
AI5 |
EVI Heat Exchanger Outlet Vapor Temperature Sensor (Low Temp Only) |
10k NTC (See Section 12 for values) |
|
AI6 |
Ambient Temperature Sensor |
10k NTC (See Section 12 for values) |
|
AI7 |
Liquid Line Temperature Sensor (Low Temp Only) |
10k NTC (See Section 12 for values) |
|
DI3 |
Future Use |
Future Use |
|
EV |
Liquid or Vapor Injection Valve |
12VDC Stepper |
|
Other Connections |
|
|
Label |
Functions |
|
VNR |
Remote Display Connection |
|
Connect + to + and – to - |
|
|
RS485 |
RS-485 Communications |
|
CANBUS |
Future Use |
|
B.BKP |
Future Use |
|
H-K |
Hotkey programming (use with part # 043-0171-01 to reset control) |
|
A A 1 2 |
052-7287-01
Low Temp 1-Phase 4-5 HP 2 Condenser Fans

052-7287-02
Medium Temp 1-Phase 1.5-3 HP 1 Condenser Fan
|
A A 1 2 |
052-7287-04
Medium Temp 3-Phase 4.5-6 HP 2 Condenser Fans
|
A A 1 2 |
052-7287-05
Low Temp 3-Phase 2-3 HP 1 Condenser Fans
|
A A 1 2 |
052-7287-13
Low Temp 3-Phase 4-6 HP 2 Condenser Fans
|
A A 1 2 |
052-7287-14
Medium Temp 3-Phase 1.5-3 HP 1 Condenser Fan
|
A A 1 2 |
052-7287-15
Medium Temp 1-Phase 4.5-5 HP 2 Condenser Fans


Evaporator Wiring Typical Unit Cooler
|
|
Refrigerant Liquid Temperature Entering TXV |
||||||||||||||
|
0 |
10 |
20 |
30 |
40 |
50 |
60 |
70 |
80 |
90 |
100 |
110 |
120 |
130 |
140 |
|
|
R-22 |
1.56 |
1.51 |
1.45 |
1.40 |
1.34 |
1.29 |
1.23 |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.88 |
0.82 |
0.76 |
|
R-404A |
2.00 |
1.90 |
1.80 |
1.70 |
1.60 |
1.50 |
1.40 |
1.30 |
1.20 |
1.10 |
1.00 |
0.90 |
0.80 |
0.70 |
0.50 |
|
R-507 |
2.00 |
1.90 |
1.80 |
1.70 |
1.60 |
1.50 |
1.40 |
1.30 |
1.20 |
1.10 |
1.00 |
0.90 |
0.80 |
0.70 |
0.50 |
|
R-134a |
1.70 |
1.63 |
1.56 |
1.49 |
1.42 |
1.36 |
1.29 |
1.21 |
1.14 |
1.07 |
1.00 |
0.93 |
0.85 |
0.78 |
0.71 |
|
R-407A |
1.75 |
1.68 |
1.61 |
1.53 |
1.46 |
1.39 |
1.31 |
1.24 |
1.16 |
1.08 |
1.00 |
0.92 |
0.84 |
0.76 |
0.68 |
|
R-407C |
1.69 |
1.62 |
1.55 |
1.49 |
1.42 |
1.35 |
1.28 |
1.21 |
1.14 |
1.07 |
1.00 |
0.93 |
0.86 |
0.79 |
0.72 |
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature of 0°F. However, they may be used for any evaporator temperature from - 40°F to + 40°F since the variation in the actual factors across this range is insignificant.
- Alarm Codes
|
Code |
Description |
Alarm Level |
Diagnostic Resolution |
Possible Fix |
|
E01 |
Suction pressure transducer error |
Alarm |
Check wire connection to the top of the controller (A1) Check to ensure suction pressure is below 135 PSIG |
Replace faulty suction pressure transducer |
|
E02 |
Condenser temperature sensor error |
Alarm |
Check wire connection to the top of the controller (A2) |
Replace faulty temperature sensor |
|
E03 |
Discharge line temperature sensor error |
Alarm |
Check wire connection to the top of the controller (A3) |
Replace faulty temperature sensor |
|
E04 |
EVI heat exchanger vapor inlet temperature error (XFALs only) |
Alarm |
Check wire connection to the top of the controller (A4) |
Replace faulty temperature sensor |
|
E05 |
EVI heat exchanger vapor outlet temperature error (XFALs only) |
Alarm |
Check wire connection to the top of the controller (A5) |
Replace faulty temperature sensor |
|
E06 |
Ambient temperature sensor error |
Alarm |
Check wire connection to the top of the controller (A6) |
Replace faulty temperature sensor |
|
E07 |
Liquid line temperature sensor error (XFALs only) |
Alarm |
Check wire connection to the top of the controller (A7) |
Replace faulty temperature sensor |
|
E09-E10 |
Current sensor error |
Alarm |
Check wires are properly routed through controller current transducers per wiring diagram |
Replace faulty controller |
|
E11-E13 |
Voltage sensor error |
Alarm |
Check wires are connected to voltage sensing connections (R, S, T) per wiring diagram |
Replace faulty controller |
|
E20 L20 |
Lost phase error/ lockout (Three phase only) |
Alarm Lockout |
Check power to unit |
Check wires are connected to voltage sensing connections (R, S, T) per wiring diagram |
|
E21 L21 |
Phase sequence error / lockout (Three phase only) |
Alarm Lockout |
Reverse two phases incoming power to unit |
Check wires are connected to voltage sensing connections (R, S, T) per wiring diagram |
|
E22 |
Phase imbalance (Three phase only) |
Alarm |
Check incoming electrical power |
Correct incoming voltage supply |
|
E23 L23 |
Over current error/ lockout |
Alarm Lockout |
Confirm system operation to find out what is causing the compressor to pull excessive current |
|
|
E24 L24 |
Open run circuit error/ lockout |
Alarm Lockout |
Check run capacitor |
Check start component wiring per diagram Check wires are properly routed through controller current transducers per wiring diagram |
|
Code |
Description |
Alarm Level |
Diagnostic Resolution |
Possible Fix |
|
E25 L25 |
Open start circuit error/ lockout |
Alarm Lockout |
Check start capacitor |
Check start component wiring per diagram Check wires are properly routed through controller current transducers per wiring diagram |
|
E26 L26 |
Under voltage alarm/ lockout |
Alarm Lockout |
Check incoming power |
|
|
E27 L27 |
Over voltage alarm/ lockout |
Alarm Lockout |
Check incoming power |
|
|
E28 |
Compressor protector trip |
Warning |
Check to see if compressor is tripped on protector |
Check to see if contactor is functioning properly Check contractor control circuit wiring per wiring diagram |
|
E40 L40 |
High pressure switch trip/ lockout |
Alarm Lockout |
Check system cause of high pressure trip Check if circuit breaker is tripped (It provides power to the high pressure switch) |
Ensure wiring to terminal C2 of the controller is correct per the wiring diagram and C2 is receiving power. Verify high pressure switch is working properly or needs replaced |
|
E44 L44 |
Discharge line temperature alarm/ lockout |
Alarm Lockout |
Check system cause of high DLT |
Faulty temperature sensor. Check sensor values versus section 12. |
|
E46 |
High condenser temperature alarm |
Alarm |
Check to see what is causing the system to run at a higher condensing temperature |
Faulty temperature sensor. Check sensor values versus section 12. |
|
E47 |
Over injection (XFALs only) |
Warning |
|
|
|
E48 |
Refrigerant shortage (XFALs only) |
Warning |
Check refrigerant charge |
EVI injection valve may not be clogged or blocked |
|
E50 |
High side flood back alarm |
Warning |
Check to see if proper superheat is being maintained |
|
|
E80 |
Rtc warning, date not correct |
Warning |
Set the real time clock |
|
|
E81 |
Rtf warning, communication error |
Warning |
Reload factory settings with the hotkey and reset the real time clock |
Replace faulty controller |
|
E82-E85 |
Configuration Errors |
Alarm |
Reload factory settings with the hotkey |
Replace faulty controller |
|
L86 |
EEPROM Memory Error |
Lockout |
Reload factory settings with the hotkey |
Replace faulty controller |
- Sensor Values
Discharge Line
Temperature Sensor Resistance
Temperature Sensor Resistance (Excludes DLT)
|
|
Label |
Description |
Default |
Range |
|
Default Display Value |
|||
|
|
Current Suction Pressure (PSIG) |
|
|
|
Adjustable in Programming Menu |
|||
|
Compressor |
|||
|
Cin / |
Compressor cut in pressure set point (PSIG) |
25.0 |
Cou - 135 |
|
CoU / |
Compressor cut out pressure set point (PSIG) |
15.0 |
0 - Cin |
|
rEF / |
Refrigerant Selection for Regulation |
R404A |
All unit Refs |
|
Low Side Control |
|||
|
idF / |
interval between defrost cycles (hour) |
8 |
0 - 120 |
|
MdF / |
Maximum length for defrost (min) |
45 |
0 - 255 |
|
EdF / |
Defrost interval mode |
in |
nu, in, RTC |
|
Ld1 / |
Workday defrost start 1 (hour) |
6:00 |
nu, 0:00 - 23:50 |
|
Ld2 / |
Workday defrost start 2 (hour) |
13:00 |
nu, 0:00 - 23:50 |
|
Ld3 / |
Workday defrost start 3 (hour) |
21:00 |
nu, 0:00 - 23:50 |
|
Ld4 / |
Workday defrost start 4 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Ld5 / |
Workday defrost start 5 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Ld6 / |
Workday defrost start 6 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Real Time Clock |
|||
|
Min / |
Current minute |
|
0 - 59 |
|
Hr / |
Current hour |
|
0 - 23 |
|
MdY / |
day of month |
|
1 - 31 |
|
Mon / |
month |
|
1 - 12 |
|
YEr / |
year |
|
0 - 99 |
|
Password |
|||
|
PAS / |
Enter into PR2 level |
321 |
(blank) |
|
Adjustable from Advanced Options Menu |
|||
|
Probe Configuration |
|||
|
P1F / |
Probe P1 calibration (PSIG) |
0.0 |
-12.0 - 12.0 |
|
Display |
|||
|
Lod / |
Remote Display visualization |
P1 |
P1 - P7 |
|
Compressor |
|||
|
LAS / |
Ambient temperature required to initiate low ambient on time (°F) |
-20 |
-40 - 230 |
|
LMO / |
Low ambient minimum on time (sec) |
6 |
0 - 255 |
|
Label |
Description |
Default |
Range |
|
Compressor Safety |
|||
|
odS / |
Output delay at start up (sec) |
6 |
0 - 255 |
|
Con / |
Compressor On time with faulty probe (min) |
3 |
0 - 255 |
|
CoF / |
Compressor OFF time with faulty probe (min) |
3 |
0 - 255 |
|
2oF / |
Compressor Minimum Off Time (sec) |
120 |
1 - 900 |
|
HPn / |
Number of high pressure switch activation before compressor lock |
5 |
0 - 15 |
|
bMP / |
Bump start enable |
YES |
no, yes |
|
dLn / |
Number of activation of DLT in a hour to lock compressor |
4 |
0 - 15 |
|
Condenser Fan |
|||
|
MCS / |
Minimum Condenser set point (°F) |
70 - XFAP 80 - XFAL |
-40 - 230 |
|
Low Side Control |
|||
|
dFd / |
Display during defrost |
dEF |
DEF, Setpoint, Initial Pressure, End Pressure |
|
Fdt / |
Drip time (min) |
0 |
0 - 120 |
|
dPo / |
Defrost at power-on |
NO |
no, yes |
|
Sd1 / |
Holiday defrost start 1 (hour) |
6:00 |
nu, 0:00 - 23:50 |
|
Sd2 / |
Holiday defrost start 2 (hour) |
13:00 |
nu, 0:00 - 23:50 |
|
Sd3 / |
Holiday defrost start 3 (hour) |
21:00 |
nu, 0:00 - 23:50 |
|
Sd4 / |
Holiday defrost start 4 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Sd5 / |
Holiday defrost start 5 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Sd6 / |
Holiday defrost start 6 (hour) |
nu |
nu, 0:00 - 23:50 |
|
Hd1 / |
First Weekly holiday |
nu |
Sun - Sat |
|
Hd2 / |
second weekly holiday |
nu |
Sun - Sat |
|
FnC / |
Fans operating mode |
on |
cn, on, cy, oy |
|
Compressor Protection |
|||
|
MC2 / |
Adjustable current limit before trip (Amps) |
MCA |
0 - MCA |
|
oCn / |
Over Current Trips before lockout |
5 |
0 - 15; 0 = always automatic restart |
|
PEn / |
loss of phase trips number before lockout |
5 |
0 - 15; 0 = always automatic restart |
|
Utn / |
compressor trips before lockout |
5 |
0 - 15; 0 = always automatic restart |
|
PiC / |
Generate warning or shut the regulation when phase imbalance |
Trip |
Warning, Trip |
|
Serial Address |
|||
|
Adr / |
Serial address |
1 |
1 - 247 |
The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.































































































































































