Mar 23, 2025
We have come across some jobs in the past where the furnace 3 amp fuse blows when the AC or Heat Pump is activated. Diagnosis is below.
Diagnosis:
- Replace Fuse
- Restart call or heat pump or Air Conditioner
- Does unit fuse pop soon after the unit starts? Or immediately?
- Immediately- Verify contactor and wiring. Shorted Contactor is usually the culprit.
- Soon after - This is typically due to one of the high or low pressure switches in the condenser. Use jumpers to jump past the switches, test operation.
For replacement:
Typically these are brazed in to the units refrigeration circuit. It is easiest to get a tee for your service valve and a new pressure switch of the same rating.