Air Conditioning Quick Re-fresh
print icon

Air Conditioning Quick Reference Guide

As A/C season approaches, it's essential to ensure systems run efficiently to prevent call-backs and maintain customer satisfaction. Here are key diagnostic and performance checks:

1. Airflow First

  • 400 CFM per ton (e.g., 3 tons = 1200 CFM, 2 tons = 800 CFM).
  • Check filters, open registers, zone dampers, and ESP levels.
  • Adjust blower speeds carefully (higher speeds aren’t always better).

2. Superheat – Compressor Protection

  • Formula: Line Temp – Gauge Temp (Line temp should always be higher).
  • Baseline: 10°F (Use manufacturer charts for target values).

3. Gauge Temperature Readings

  • Low Side (Blue Gauge): Indoor Coil TempTarget: 40-45°F.
  • High Side (Red Gauge): Outdoor Coil TempTarget: 95-105°F.

4. Subcooling – Liquid Line Charge

  • Formula: Gauge Temp – Line Temp (Gauge temp should always be higher).
  • Baseline: 10°F (Use manufacturer charts for accuracy).

5. Low Ambient Charging Precaution

  • Avoid charging below 65°Fcharge by weight in cold conditions.

6. Inspect & Replace Worn Components

  • Check capacitors, contactors, and line insulation for wear.

7. Run Cycle Best Practices

  • Minimum 15-minute cycles to ensure proper dehumidification & equipment longevity.
  • Short cycling reduces efficiency and may cause damage