Here are the error codes on the Tempstar and Heil *97CMN Series Furnaces.
| Code | Description | Recommended Action |
|---|---|---|
| 10.1 | L1 POLARITY FAULT | Rapid flash LED. |
| 10.2 | Refrigerant leak detected, operate blower. | Operate blower. |
| 12.1 | “W” ON at power up – Normal operation. | Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or when (R-W opens) during the blower on-delay period. |
| 13.1 | LIMIT CIRCUIT LOCKOUT | Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch*(if used) is open longer than 3 minutes. Control will auto-reset after 3 hours. |
| 14.1 | IGNITION LOCKOUT | System failed to ignite gas and prove flame in 4 attempts. Control will auto-reset after 3 hours. |
| 14.2 | FLAME LOST | 3 times after 70s of heating. |
| 14.3 | LOCKOUT | 7 loss of flame events during a heat request. |
| 14.4 | LOCKOUT | 7 pressure switch open events during a heat request. |
| 15.1 | BLOWER RPM LOCKOUT | Lockout occurs when no blower rpm is detected. |
| 15.2 | LOCKOUT | Failed to reach 500 rpm during startup. Check for loose blower wire connections or failed blower motor. |
| 21.1 | 24VAC sensed on gas valve when it shouldn’t be. | Turn off power and wait 5 minutes to retry. Check for stuck closed gas valve relay on control or miswire/short at gas valve wire. |
| 22.1 | Stuck open or leaky gas valve. | |
| 23.4 | LPS pressure switch | Check for obstructed pressure tube or a pressure switch stuck closed. |
| 23.5 | HPS pressure switch | Check for obstructed pressure tube or a pressure switch stuck closed. |
| 23.6 | MPS pressure switch | Check for obstructed pressure tube or a pressure switch stuck closed. |
| 24.1 | FUSE FAULT | Check for short circuit in secondary voltage (24-V) wiring, including thermostat leads. Disconnect thermostat leads to isolate short circuit. |
| 25.1 | NO PROGRAM info in micro, no heating operation. | Reprogram control. |
| 25.2 | CORRUPTED PROGRAM FILE | Reprogram control using service app or super plug (supplied separately). |
| 25.4 | MAIN PROGRAM INVALID | Using backup program to operate. Reprogram control to correct issue. Control still operates normally. |
| 25.5 | INSTALLER SETTINGS CORRUPTED | Try reselecting installer settings, or reprogram control. Control will operate using default installer settings. |
| 25.6 | WRONG PROGRAM for control used | Reprogram control so program matches control used. No heating operation. If program in furnace control is missing, not recognized, or corrupted. Reprogram control with correct program # as listed on the rating plate. Replace control if issue remains. |
| 27.1 | Program in super plug is missing, not recognized, or corrupted. | Remove super plug, then retry. If still have 27 code, try a different super plug. If still fails, replace control. |
| 27.2 | Program in super plug is missing, not recognized, or corrupted. | Remove super plug, then retry. If still have 27 code, try a different super plug. If still fails, replace control. |
| 27.3 | Program in super plug is missing, not recognized, or corrupted. | Remove super plug, then retry. If still have 27 code, try a different super plug. If still fails, replace control. |
| 31.1 | Medium heat pressure switch input OFF when it should be ON | |
| 31.2 | Medium heat pressure switch input ON when it should be OFF | |
| 31.6 | Open HPS – HPS failed to close in 75s when transitioning from low to high heat | Check for excessive wind, restricted vent, defective inducer motor, low inlet gas pressure (if LGPS used), inadequate combustion air supply, proper vent sizing, disconnected/obstructed pressure tubing, condensate drainage blocked or restricted. |
| 51.1 | OAT OPEN – Outdoor Air Temperature sensor connection is open | Check for loose connection at control board screw terminals. |
| 51.2 | OAT SHORT – Outdoor Air Temperature sensor wires are shorted | Check for loose connection at control board screw terminals. |
| 32.2 | OPEN MAIN PRESSURE SWITCH | If LPS is open longer than 5 minutes or has reopened, inducer shuts off for 15 minutes before retry. |
| 52.1 | SAT OPEN – Supply Air Temperature sensor connection is open | Check for loose connection at control board screw terminals. |
| 52.2 | SAT SHORT – Supply Air Temperature sensor wires are shorted | Check for loose connection at control board screw terminals. |
| 33.1 | A SWITCH HAS OPENED IN THE MAIN LIMIT | Indicates the limit or flame rollout is open. Blower will run for 4 minutes or until open switch remakes, whichever is longer. |
| 53.1 | RAT OPEN – Return Air Temperature sensor connection is open | Check for RAT firmly plugged into control board, damaged RAT sensor, dirty filter, or restricted duct system. |
| 53.2 | RAT SHORT – Return Air Temperature sensor is shorted | Check for RAT firmly plugged into control board, damaged RAT sensor, dirty filter, or restricted duct system. |
| 41.2 | NO BLOWER RPM – No blower rpm when blower motor is running | Check for loose blower wire connections, failed blower motor. |
| 41.3 | Failed to reach 500rpm at startup | Check for loose blower wire connections or failed blower motor. |
| 42.1 | No inducer RPM at startup | |
| 42.2 | No RPM when inducer motor is running | |
| 42.3 | Exceeding inducer RPM limit | |
| 43.1 | HPS closed before LPS | |
| 45.1 | CONTROL FAILURE – flame circuit fault, memory mismatch or sequence error | Replace control. |
| 45.2 | CONTROL FAILURE – gas valve relay will not close | Replace control. |
| 45.3 | CONTROL FAILURE – EEPROM memory issue | Replace control. |
| 45.4 | CONTROL FAILURE – Micro loss of Comm | Replace control. |
| 34.1 | IGNITION FAULT – During four consecutive ignition trials. | Check for gas valve turned off, manual shut-off valve, green/yellow wire connection, or flame sensor grounding. |
| 34.5 | AFTER SUCCESSFUL IGNITION (flame proven) Low heat flame loss before heating blower on delay. | |
| 34.6 | AFTER SUCCESSFUL IGNITION (flame proven) High heat flame loss before heating blower on delay. | |
| 34.7 | AFTER SUCCESSFUL IGNITION (flame proven) Low flame loss after heating blower on delay. | |
| 34.8 | AFTER SUCCESSFUL IGNITION (flame proven) Low flame loss after heating blower on delay. | |
| 35.1 | Modulating gas valve not communicating. |