Here's a summary of the bulletin regarding R-32 refrigerant leak mitigation for HVAC systems using electronic accessories:
See attached bulletin for wiring diagrams and the rest of the information.
Purpose:
To inform technicians about safety procedures when R-32 refrigerant is used in HVAC systems with electronic accessories (e.g., zoning systems, EACs, UV lamps, humidifiers).
Key Points:
-
RDS (Refrigerant Detection System):
-
Detects R-32 leaks inside the indoor unit.
-
Shuts off heating, cooling, and fan modes.
-
Runs the indoor blower at max CFM to dissipate refrigerant.
-
-
A2L Accessory/Zoning Control (Kit #0230K00007):
-
Works with RDS to:
-
Open all zone dampers to 100%.
-
De-energize potential ignition sources (e.g., EACs, UV lamps, HRVs/ERVs).
-
-
After leak is cleared, restores power and returns zoning control to normal.
-
Wiring & Installation:
-
NEC requires strain relief for 120V wiring to the Accessory/Zoning Control.
-
Control box must be mounted inside a metal enclosure (min. 10” x 8” x 3”).
-
Enclosure must accommodate connectors and wiring; cover optional if wiring remains within the control box.
Accessory Connection Guidelines:
| Accessory | Power Connection Instructions | Leak Alarm Behavior |
|---|---|---|
| Electronic Air Cleaner (EAC) | Connect via Accessory/Zoning Control | Power cut during leak |
| UV Lamp | Connect via Accessory/Zoning Control | Power cut during leak |
| HRV/ERV | Connect via Accessory/Zoning Control | Power cut during leak |
| Humidifier | Typically powered via HUM terminals on furnace | Not affected by RDS, zoning control not required |
| Dehumidifier | If tied to ductwork, connect via Accessory/Zoning Control | Power cut during leak |
Alternative Option (No Zoning):
-
Use DPDT (Double Pole, Double Throw) relays (Part #0130M00908 or equivalent) if the system has no zoning and only one or two accessories.
-
Relay must open circuits during a leak alarm.
-
Must match the accessory’s amp rating.
-